Settings
You will find detailed information about the settings in:
Chapter 4.2.2 "General settings and
Solenoid valve
OFF
ON >
Non-maintained
command mode
Separate failsafe
function from
control function
Execution time
Table 4-16: Solenoid valve control function settings
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
definitions".
OFF control command (CLOSE)
(connection with arbitrary socket
usually with "Enabled control command - OFF" socket)
ON control command (OPEN)
(connection with arbitrary socket
usually with "Enabled control command - ON >" socket)
• Deactivated
• Activated
• Deactivated:
Safety-oriented tripping via the DM-F module also affects the
SIMOCODE pro control function, so that additional fault
messages are avoided.
This setting is selected for applications where safety-oriented
tripping directly affects the motor controlled by SIMOCODE pro.
• Activated:
Safety-oriented tripping via the DM-F module does not affect the
SIMOCODE pro control function.
This setting is selected for applications where safety-oriented
tripping does not affect the motor controlled by SIMOCODE pro.
Time required to reach end position.
Range 0 - 6553.5 seconds (default: 1.0 s)
Motor control
Description
,
,
4-53