Standard functions
Test phases
The following table shows the test phases carried out when the "TEST/
RESET" button is pressed for the required length of time:
Test
Status
phase
"DEVICE" LED
< 2s
"GEN.FAULT" LED
Contactor control
Show QL
"DEVICE" LED
2s - 5s
"GEN.FAULT" LED
Contactor control
"DEVICE" LED
> 5s
"GEN.FAULT" LED
Contactor control
LED lit/activated
1) "Fault" only displayed after 2 s
Table 10-2: The states of the status LEDs/contactor controls during testing
Test settings
Test 1 to 2 -
Input
Test/Reset
buttons blocked
Table 10-3: Test settings
10-6
Without main current
O.K.
Fault
Hardware test/lamp test
Orange
Unchanged
Unchanged
Results of the hardware test/lamp test
Green
Unchanged
Deactivated
Relay test
Green
Deactivated
Deactivated
LED flashing
LED flickering
Control of the "Test" function block from any signal (any sockets
e.g. device inputs, control bits from PROFIBUS DP , etc.)
The blue Test/Reset buttons on the basic unit and the operator
panel are usually intended for acknowledging faults and for carrying
out a device test.
The buttons can be blocked via "Test/Reset buttons blocked". These
can then be used for other purposes. On the operator panel with
display, blocking is carried out via the corresponding menu function.
(Default: Unblocked)
With main current
1)
O.K.
Green
Orange
Unchanged
Red
Green
Unchanged
Red
Green
Deactivated
LED OFF
Description
GWA 4NEB 631 6050-22 DS 03
Fault
Green
Unchanged
Red
Deactivated
Red
Deactivated
,
SIMOCODE pro