Data formats and data records
Byte
Designation
Bit
(PRM group)
12.0
Bit parameters (16)
12.0
No configuration fault due to
OP
12.1
Start-up parameter block
active
12.2
Test/Reset buttons blocked
12.3
Bus and PLC/PCS - Reset
12.4
Reserved
12.5
Reserved
12.6
Reserved
12.7
Reserved
13.0
Diagnostics for process events Bit
13.1
Diagnostics for process
warnings
13.2
Diagnostics for process faults Bit
13.3
Diagnostics for device faults
13.4
Reserved
13.5
Reserved
13.6
Bus monitoring
13.7
PLC/PCS monitoring
14.0
Overload protection - Type of
load
14.1
Overload protection - Reset
14.2
Reserved
14.3
Saving change-over command Bit
14.4
Non-maintained command
mode
14.5
Cold starting level (TPF)
14.6
Load type
14.7
Reserved
15.0
External fault 1 - Type
15.1
External fault 2 - Type
15.2
External fault 3 - Type
15.3
External fault 4 - Type
15.4
External fault 1 - Activity
15.5
External fault 2 - Activity
15.6
External fault 3 - Activity
15.7
External fault 4 - Activity
Table B-12: Data record 130 - Basic device parameters 1 (Cont.)
B-22
Type
Range
De-
fault
Bit
0, 1
0
Bit
0, 1
1
Bit
0, 1
0
Bit
0, 1
0
Bit
0
Bit
0
Bit
0
Bit
0
0, 1
0
Bit
0, 1
1
0, 1
1
Bit
0, 1
1
Bit
0
Bit
0
Bit
0, 1
1
Bit
0, 1
1
Bit
0, 1
0
Bit
0, 1
0
Bit
0
0, 1
0
Bit
0, 1
0
Bit
0, 1
0
Bit
0, 1
0
Bit
0
Bit
0, 1
0
Bit
0, 1
0
Bit
0, 1
0
Bit
0, 1
0
Bit
0, 1
0
Bit
0, 1
0
Bit
0, 1
0
Bit
0, 1
0
Note
0 = Manual, 1 = Auto
0 = 3-phase, 1 = 1-phase
0 = Manual, 1 = Automatic
0 = NO contact, 1 = NC contact
0 = Motor, 1 = Resistive load
0 = NO contact, 1 = NC contact
0 = Always, 1 = Only motor ON
GWA 4NEB 631 6050-22 DS 03
Informa-
tion
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
IM UM
IM UM
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
BU1 BU2
SIMOCODE pro