Motor control
Settings
You will find detailed information about the settings in:
Chapter 4.2.2 "General settings and
Star-delta starter
OFF
ON >
FB ON
Non-maintained
command mode
Separate failsafe
function from
control function
Load type
Feedback time
Execution time
Change-over pause Range 0 - 655.3 seconds (10 ms increments) (0.00 s)
Max.
star time
Current measuring
module installed
Table 4-10: Star-delta starter settings
1)Notice
If a current/voltage measuring module is in use, the transformer must be
connected to the supply cable!
4-32
definitions".
OFF control command
(connection with arbitrary socket
usually with "Enabled control command - OFF" socket)
ON control command
(connection with arbitrary socket
usually with "Enabled control command - ON >" socket)
Auxiliary control input "Feedback ON"
(connection with arbitrary socket
usually with "Status - Motor current flowing" socket)
• Deactivated
• Activated
• Deactivated:
Safety-oriented tripping via the DM-F module also affects the
SIMOCODE pro control function, so that additional fault
messages are avoided.
This setting is selected for applications where safety-oriented
tripping directly affects the motor controlled by SIMOCODE pro.
• Activated:
Safety-oriented tripping via the DM-F module does not affect the
SIMOCODE pro control function.
This setting is selected for applications where safety-oriented
tripping does not affect the motor controlled by SIMOCODE pro.
You can choose between:
• Motor
• Resistive load (see
definitions")
Range 0 - 25.5 seconds (0.5 s)
Range 0 - 6553.5 seconds (1 s)
Time-dependent switching from star to delta.
Range 0 - 255 seconds (20 s)
The set current and the switching levels for star-delta switching
1)
depend on the mounting place of the current measuring module.
• In delta: Set current I
• In supply cable: Set current I
Description
,
,
,
Chapter 4.2.2 "General settings and
is reduced to I
x 1/√3 (default)
s
n
= I
(rated current of the motor)
s
n
GWA 4NEB 631 6050-22 DS 03
SIMOCODE pro