Siemens SIMOCODE pro System Manual page 314

Motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

3UF50 compatibility mode
Diagram of diagnostics data
The following table shows the diagnostics data in the 3UF50-compatibility
mode:
Byte
Setup 3UF50 - device-specific
Bit
diagnostics acc. to DP
standard SIMOCODE-DP
6
0x0E
7.0
Free
7.1
Event: DP block
7.2
Event: Emergency start
7.3
Event: HW test OK
7.4
Free
7.5
Event: Ext. event 1
7.6
Event: Ext. event 2
7.7
Event: Ext. event 3
8.0
Warning: Ext. Warning
8.1
Warning: Unbalance > 40%
8.2
Event: Failure PLC-CPU
8.3
Warning: Sensor short circuit
8.4
Event: Cooling down period
active
8.5
Status: TPF
8.6
Free
8.7
Free
9.0
Warning: Earth fault
9.1
Warning: Overload
9.2
Warning: Overload + unbalance
9.3
Warning: I1 response level
overshot
9.4
Warning: I1 response level
undershot
9.5
Warning: I2 response level
overshot
9.6
Warning: I2 response level
undershot
Table 9-3: Diagram of the diagnostics data in the 3UF50 compatibility mode
9-4
Byte
Setup 3UF50 - device-specific
Bit
diagnostics acc. to
SIMOCODE-DP DPV1 standard
6
0x0B
7
0x81
8
0x04
9
0x00
10.0
Free
10.1
Event: DP block
10.2
Event: Emergency start
10.3
Event: HW test OK
10.4
Free
10.5
Event: Ext. event 1
10.6
Event: Ext. event 2
10.7
Event: Ext. event 3
11.0
Warning: Ext. warning
11.1
Warning: Unbalance > 40%
11.2
Event: Failure PLC-CPU
11.3
Warning: Sensor short circuit
11.4
Event: Cooling down period
active
11.5
Status: TPF
11.6
Free
11.7
Free
12.0
Warning: Earth fault
12.1
Warning: Overload
12.2
Warning: Overload + unbalance
12.3
Warning: I1 response level
overshot
12.4
Warning: I1 response level
undershot
12.5
Warning: I2 response level
overshot
12.6
Warning: I2 response level
undershot
Equivalent in SIMOCODE pro V
Same as 3UF50 diagnostics
Event - Start-up parameter
block active
Status - Emergency start executed
• No fault - HW fault basic unit
• No fault - Module fault
• No fault - Temporary components
-
Event - Ext. fault 5
Event - Ext. fault 6
-
Warning - Ext. fault 3
Warning - Unbalance
Status - PLC/PCS (inverted)
Warning - Thermistor short circuit
Status - Cooling down period active
Status - Test position (TPF)
-
-
• Warning - Int. earth fault
or
• Warning - Ext. earth fault
Warning - Overload
Warning - Overload + phase failure
Warning - Warning level I>
Warning - Warning level I<
-
-
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03