Test/Reset - Siemens SIMOCODE pro System Manual

Motor management and control devices
Hide thumbs Also See for SIMOCODE pro:
Table of Contents

Advertisement

Standard functions
10.2

Test/Reset

Test/Reset description
The function of the "Test/Reset" button on the basic unit or on the operator
panel is generally dependent upon the operating status of the device:
• Reset function: If a fault occurs
• Test function: In other operating states.
In addition to the Test/Reset button, SIMOCODE pro allows internal Test/
Reset tripping via the "Test" function blocks. The "Test" function block
consists of one plug.
Overall, the following are available:
• Two function blocks, "Test 1" and "Test 2", for BU1 and BU2, whereby each
function block has a slightly different function:
– Test 1: Test/trips the output relays
– Test 2: Does not trip the output relays (normally for testing via the bus).
Schematic
The following schematic shows a general representation of the "Test/Reset"
function blocks:
BU "TEST/RESET" button
OP "TEST/RESET" button*
Fig. 10-2: "Test/Reset" function blocks
*) The operator panel with display does not have a Test/Reset button. The
respective functions can be carried out via the operator panel menu or via
softkeys.
10-4
"Test/Reset" function blocks
Test 1
Test 1
Test 2
Test 2
Reset 1
Reset 1
Reset 2
Reset 2
Reset 3
Reset 3
Test/Reset buttons blocked
Control functions
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03

Advertisement

Table of Contents
loading

Table of Contents