DC Reactor
A DC reactor can also increase line impedance, improve the power factor, reduce input current, increase
system power, and reduce interference generated from the motor drive. A DC reactor stabilizes the DC
bus voltage. Compared with an AC input reactor, a DC reactor is in smaller size, lower price, and lower
voltage drop (lower power dissipation).
Install a DC reactor between terminals +1 and +2. Remove the jumper, as shown in the figure below,
before installing a DC reactor.
NOTE: 115V models have no DC choke.
Applicable Reactors
115V, 50–60 Hz / One-phase - Normal Duty
Model
Current
VFD1A6MS11ANSAA
VFD1A6MS11ENSAA
VFD2A5MS11ANSAA
VFD2A5MS11ENSAA
VFD4A8MS11ANSAA
VFD4A8MS11ENSAA
115V, 50–60 Hz / One-phase - Heavy Duty
Model
Current
VFD1A6MS11ANSAA
VFD1A6MS11ENSAA
VFD2A5MS11ANSAA
VFD2A5MS11ENSAA
VFD4A8MS11ANSAA
VFD4A8MS11ENSAA
Rated
Saturation
Input / DC
Current
Reactor
(Arms)
(Arms)
(mH)
1.8
2.7
3.66
2.7
4.05
2.66
5.5
8.25
1.17
Rated
Saturation
Input / DC
Current
Reactor
(Arms)
(Arms)
(mH)
1.6
3.2
3.66
2.5
5
2.66
5
9.6
1.17
Chapter 7 Optional AccessoriesMS300
Figure 7-6
AC Input / DC Reactor
Delta Part # Weight (kg)
DR008D0366
0.8
DR011D0266
1.2
DR025D0117
2.8
AC Input / DC Reactor
Delta Part #
Weight (kg)
DR008D0366
0.8
DR011D0266
1.2
DR025D0117
2.8
59
Output
AC Output Reactor
Reactor
Delta Part # Weight (kg)
(mH)
2.54
DR005L0254
2.54
DR005L0254
1.59
DR008L0159
Table 7-12
Output
AC Output Reactor
Reactor
Delta Part # Weight (kg)
(mH)
2.54
DR005L0254
2.54
DR005L0254
2.54
DR005L0254
Table 7-13
1.5
1.5
2.5
1.5
1.5
1.5