00-20
Master Frequency Command Source (AUTO, REMOTE)
Settings
Determines the master frequency source in the "AUTO, REMOTE "mode. The default is AUTO
mode.
You can switch the AUTO, REMOTE mode with the keypad KPC-CC01 (optional) or the multi-
function input terminal (MI) to set the master frequency source.
It returns to AUTO or REMOTE mode whenever you cycle the power. If you use a multi-function
input terminal to switch between HAND (LOCAL) and AUTO (REMOTE) mode, the highest
priority is the multi-function input terminal.
The pulse of Pr.00-20 = 4 (Pulse input without direction command) is input by MI7.
When Pr.00-20 = 9, Pr.08-65 automatically set as 1 at the same time. Pr.08-65 needs to be set
as 0 for changing back to other values.
When Pr.00-20 = 7, set Pr.03-40 = 50% and Pr.03-41 (VR Positive / Negative Bias) = 4 (Bias
serves as the center). If you need to reverse the setting, set Pr.03-10 = 1.
00-21
Operation Command Source (AUTO, REMOTE)
Settings
Determines the operation frequency source in the "AUTO, REMOTE" mode.
In the HOA mode, if the multi-function input terminal (MI) function setting 41 and 42 are OFF, the
drive does not receive any operation command and JOG is invalid.
0: Digital keypad
1: RS-485 communication input
2: External analog input (Refer to Pr.03-00)
3: External UP / DOWN terminal (multi-function input terminals)
4: Pulse input without direction command
(Refer to Pr.10-16 without considering direction)
6: CANopen communication card
7: Digital keypad potentiometer knob
8: Communication card (does not include CANopen card)
9: PID controller
NOTE:
HOA (Hand-Off-Auto) function is valid only when you use with MO function
setting 42 and 56 or with KPC-CC01 (optional).
0: Digital keypad
1: External terminals
2: RS-485 communication input
3: CANopen communication card
5: Communication card (does not include CANopen card)
NOTE:
HOA (Hand-Off-Auto) function is valid only when you use with MO function
setting 42 and 56 or with KPC-CC01 (optional).
272
Default: 0
Default: 0