Chapter 14 Fault CodesMS300
ID
Display on LCD Keypad
45
Action Condition
Action Time
Fault Treatment Parameter
Reset Method
Reset Condition
Record
Cause
Incorrect settings for PG feedback
parameters
Incorrect settings for ASR
parameters and accel./decel. time
Incorrect settings of encoder
parameters
Accel./Decel. time is too short
Incorrect settings of torque limit
parameters (Pr.06-12,Pr.11-17–20)
Motor shaft lock
Mechanical brake is not released
Fault Name
PG slip error
(PGF4)
Action and Reset
Pr.10-13
Pr.10-14
Pr.10-15
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
When Pr.10-15 = 0, PGF4 is a "Warning". When the deviation
Auto
between the output frequency and motor frequency is smaller than the
encoder observer slip range, the warning is automatically cleared.
Manual When Pr.10-15 = 1 or 2, PGF4 is a "Fault". You must reset manually.
Immediately reset
When Pr.10-15 = 1 or 2, PGF4 is a "Fault", and the fault is recorded.
Reset correct values for Pr.10-13 and Pr.10-14.
Reset ASR parameters.
Set correct accel./decel time.
Reset encoder parameters (Pr.10-01).
Reset proper accel./decel. time.
Reset proper setting values for Pr.06-12 and Pr.11-17–Pr.11-20.
Remove causes of motor shaft lock.
Check the action timing of the system.
584
Fault Descriptions
Under PG mode, when the motor frequency exceeds
encoder observer slip range (Pr.10-13) and starts to
count, the fault time is longer than the detection time of
encoder observer slip (Pr.10-14), PGF4 fault occurs.
Corrective Actions