Delta MS300 Series User Manual page 369

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

Chapter 12 Descriptions of Parameter SettingsMS300
06-06
Over-Torque Detection Selection (Motor 1)
Settings
06-09
Over-Torque Detection Selection (Motor 2)
Settings 0: No function
 When you set Pr.06-06 and Pr.06-09 to 1 or 3, a warning message displays but there is no error
record.
 When you set Pr.06-06 and Pr.06-09 to 2 or 4, an error message displays and there is an error
record.
06-07
Over-Torque Detection Level (Motor 1)
Settings
06-08
Over-Torque Detection Time (Motor 1)
Settings
06-10
Over-Torque Detection Level (Motor 2)
Settings
06-11
Over-Torque Detection Time (Motor 2)
Settings
 When the output current exceeds the over-torque detection level (Pr.06-07 or Pr.06-10) and also
exceeds the over-torque detection time (Pr.06-08 or Pr.06-11), the over-torque detection follows
the setting of Pr.06-06 and Pr.06-09.
 When you set Pr.06-06 or Pr.06-09 to 1 or 3, an ot1 / ot2 warning displays while the drive keeps
running after over-torque detection. The warning remains on until the output current is smaller
than 5% of the over-torque detection level.
0: No function
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
1: Continue operation after over-torque detection during constant speed
operation
2: Stop after over-torque detection during constant speed operation
3: Continue operation after over-torque detection during RUN
4: Stop after over-torque detection during RUN
10–250% (100% corresponds to the rated current of the drive)
0.1–60.0 sec.
10–250% (100% corresponds to the rated current of the drive)
0.1–60.0 sec.
360
Default: 0
Default: 0
Default: 120
Default: 0.1
Default: 120
Default: 0.1