Delta MS300 Series User Manual page 568

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

ID
Display on LCD Keypad
12
Action Condition
Action Time
Fault Treatment Parameter
Reset Method
Reset Condition
Record
Cause
Power-off
Power voltage changes
Start up the motor with large
capacity
Sudden load
DC bus
Fault Name
Low-voltage during
deceleration
(Lvd)
Action and Reset
Pr.06-00 (Default = depending on the model)
Immediately act when the DC bus voltage is lower than Pr.06-00
NA
Manual reset
Reset when the DC bus voltage is higher than Pr.06-00 + 30 V
Yes
Improve power supply condition.
Adjust voltage to the power range of the drive.
Check the power system.
Increase the capacity of power equipment.
Reduce the load.
Increase the drive capacity.
Install DC reactor(s).
559
Fault Descriptions
DC bus voltage is lower than Pr.06-00 setting value
during deceleration
Corrective Actions
Chapter 14 Fault CodesMS300