Delta MS300 Series User Manual page 42

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

Frame B
If you install at Ta 50°C above environment, use copper wires that have a voltage rating of 600 V
and are temperature resistant to 90°C or above.
If you install at Ta 50°C environment, use copper wires that have a voltage rating of 600 V and are
temperature resistant to 75°C or 90°C.
To be UL installation compliant, you must use copper wires when installing. The wire gauge is
based on a temperature resistance of 75°C, in accordance with UL requirements and
recommendations. Do not reduce the wire gauge when using high-temperature resistant wires.
Models
VFD1A6MS21AFSAA
VFD2A8MS21AFSAA
VFD4A8MS21AFSAA
VFD4A8MS21ANSAA
VFD4A8MS21ENSAA
VFD7A5MS23ANSAA
VFD7A5MS23ENSAA
VFD1A5MS43AFSAA
VFD2A7MS43AFSAA
VFD4A2MS43ANSAA
VFD4A2MS43ENSAA
VFD4A2MS43AFSAA
VFD3A0MS53ANSAA
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, DC-,
DC+/+1, +2/B1, B2
Max. Wire
Min. Wire
Gauge
Gauge
1.5 mm
(16 AWG)
2.5 mm
(14 AWG)
2
4 mm
(12 AWG)
2
4 mm
(12 AWG)
0.75 mm
(18 AWG)
2.5 mm
(14 AWG)
0.75 mm
(18 AWG)
Chapter 5 Main Circuit TerminalsMS300
Figure 5-9
Screw Size
Max. Wire
& Torque
Gauge
(±10%)
2
2.5 mm
2
(14 AWG)
4 mm
(12 AWG)
M4
15 kg-cm
(13.0 lb-in.)
(1.47 Nm)
2
2.5 mm
(14 AWG)
2
2
2.5 mm
(14 AWG)
33
Grounding Terminals
Screw Size &
Min. Wire
Torque
Gauge
(±10%)
2
2
2.5 mm
(14 AWG)
2
2
4 mm
(12 AWG)
15 kg-cm
(13.0 lb-in.)
(1.47 Nm)
2
2
2.5 mm
(14 AWG)
2
2
2.5 mm
(14 AWG)
Table 5-4
M4

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents