Chapter 12 Descriptions of Parameter SettingsMS300
 When Pr.02-09 is set to 3:
The increasing / decreasing frequency command (F) operates according to the exponential
curve.
 When Pr.02-09 is set to 4:
The tiered increasing or decreasing Frequency command (F) operates according to the setting
of Pr.02-10 per very 100 ms.
02-11
Multi-Function Input Response Time
Settings
 Use this parameter to set the response time of the digital input terminals MI1–MI7.
 This function is to delay and confirm the digital input terminal signal. The time for delay is also
the time for confirmation. The confirmation prevents interference that could cause error in the
input to the digital terminals. In the meanwhile, it delays the response time though confirmation
improves accuracy.
0.000–30.000 sec.
306
Default: 0.005