08-18
Sleep Mode Function Setting
Settings
0: The unit for Pr.08-10 and that for Pr.08-11 switch to frequency. The settings are between
0.00–599.00 Hz.
1: The unit for Pr.08-10 and that for Pr.08-11 switch to percentage. The settings are between
0.00–200.00%.
08-19
Wake-up Integral Limit
Settings
Reduces the reaction time from sleep to wake-up.
Defines the wake-up integral frequency limit = (Pr.01-00 × Pr.08-19%)
08-21
Enable PID to Change the Operation Direction
Settings
08-22
Wake-up Delay Time
Settings
Refer to Pr.08-18 for more information.
08-23
PID Control Flag
Settings
bit 0 = 1: PID running in reverse function is valid only when Pr.08-21 = 1.
bit 0 = 0: If the PID calculated value is positive, the direction is forward. If the PID calculated
value is negative, the direction is reverse.
When the bit1 setting changes, the Kp gain does not change.
For example: Kp = 6. When Pr.08-23 bit1 = 0, Kp = 6.0; when Pr.08-23 bit1 = 1, Kp = 6.00.
0: Refer to PID output command
1: Refer to PID feedback signal
0.0–200.0%
0: Operation direction cannot be changed
1: Operation direction can be changed
0.00–600.00 sec.
bit 0 = 1, PID running in reverse follows the setting for Pr.00-23.
bit 0 = 0, PID running in reverse refers to PID's calculated value.
bit 1 = 1, two decimal places for PID Kp
bit 1 = 0, one decimal place for PID Kp
Chapter 12 Descriptions of Parameter SettingsMS300
405
Default: 0
Default: 50.0
Default: 0
Default: 0.00
Default: 2