Chapter 12 Descriptions of Parameter SettingsMS300
Explanation 5
Setting value 25: when displayed value reaches 100.00%, the drive shows "oL" as an overload
warning.
Explanation 6
Setting value 38:
bit 0: The drive is running forward.
bit 1: The drive is running backward.
bit 2: The drive is ready.
00-05
Coefficient Gain in Actual Output Frequency
Settings
 Sets the user-defined unit coefficient gain. Set Pr.00-04 = 31 to display the calculation result on
the screen (calculation = output frequency × Pr.00-05).
00-06
Firmware Version
Settings
00-07
Parameter Protection Password Input
Settings
Display
 This parameter allows you to enter your password (which is set in Pr.00-08) to unlock the
parameter protection and to make changes to the parameter.
 To avoid problems in the future, be sure to write down the password after you set this parameter.
 Pr.00-07 and Pr.00-08 are used to prevent personnel from setting other parameters by accident.
 If you forget the password, clear the password setting by entering 9999 and pressing the ENTER
key, then enter 9999 again and press ENTER within 10 seconds. After decoding, all the settings
return to default.
 When setting is under password protection, all the parameters read 0, except Pr.00-08.
00-08
Parameter Protection Password Setting
Settings
 This parameter is for setting the password protection. Password can be set directly the first time.
After you set the password, the value of Pr.00-08 is 1, which means password protection is
activated. At this time, if you want to change any of the parameter settings, you must enter the
correct password in Pr.00-07 to deactivate the password temporarily, and this would make Pr.00-
08 become 0. After you finish setting the parameters, reboot the motor drive and the password is
activated again.
0.00–160.00
Read only
0–65535
0–4 (the number of password attempts)
0–65535
0: No password protection or password is entered correctly (Pr.00-07)
1: Password has been set
bit 3: Errors occurred on the drive.
bit 4: The drive is running.
bit 5: Warnings occurred on the drive.