Settings
Functions
UVW output
45
electromagnetic valve
switch
46
Master dEb output
Output control for
50
CANopen
Analog output control for
51
RS-485 interface
Output control for
52
communication cards
53
Fire mode indication
Chapter 12 Descriptions of Parameter SettingsMS300
Use this function with external terminal input = 49 (drive enabled)
and external terminal output = 45 (electromagnetic valve enabled),
and then the electromagnetic valve is ON or OFF according to the
status of the drive.
When dEb rises at the master, MO sends a dEb signal to the
slave. Output the message when the master triggers dEb. This
ensures that the slave also triggers dEb. Then the slave follows
the deceleration time of the master to stop simultaneously with
the master.
Control the multi-function output terminals through CANopen.
The mapping table of the CANopen DO is shown in the following
table:
Physical
Setting for Related
Terminal
Parameters
RY1
Pr.02-13=50
MO1
Pr.02-16=50
MO2
Pr.02-17=50
Refer to Section 15-3-5 for more information.
For RS-485 communication control output.
Control the output through the communication cards
(CMM-PD02, CMM-DN02, CMM-EIP02, CMM-COP02, CMM-EC02)
Physical
Setting of Related
Terminal
Parameters
RY
Pr.02-13 = 51
MO1
Pr.02-16 = 51
MO2
Pr.02-17 = 51
Activates when MI setting 58 or 59 is enabled.
311
Descriptions
Attribute
Corresponding Index
2026-41
RW
bit 0 of initial value 0x01
2026-41
RW
bit 3 of initial value 0x01
2026-41
RW
bit 4 of initial value 0x01
Corresponding
Attribute
RW
RW
RW
Address
bit 0 of 2640
bit 3 of 2640
bit 4 of 2640