ID No.
Display on LCD Keypad
57
Action Condition
Action Time
Warning Setting Parameter
Reset Method
Reset Condition
Record
Cause
There is no "END" command
during PLC operation
Warning Name
No end command
(PLEd)
Action and Reset
The "End" command is missing until the last command is executed, the PLEd
warning occurs.
Immediately act when the fault is detected
NA
Check if the program is correct and download the program again. If the fault
does not exist, the warning automatically clears.
N/A
N/A
1. Disable PLC
2. Reset the PLC program (Pr.00-02 = 6)
3. Enable PLC
4. Re-download the PLC program
515
Chapter 13 Warning CodesMS300
Description
PLC end command is missing
Corrective Actions