Chapter 12 Description of Parameter SettingsMS300
 Basic motor parameters adjustment
Parameter reset:
1.
Reset Pr.00-02 = 9 (50 Hz) or 10 (60 Hz) to the default value.
Select PM motor type:
2.
Pr.05-33 = 0 (IM)
Motor nameplate parameter setting:
3.
Parameter
Pr.01-01
Pr.01-02
Pr.05-01
Pr.05-02
Pr.05-03
Pr.05-04
Motor auto-tuning:
4.
Press RUN to start auto-tuning of IM magnetic flux curve dynamic test for Pr.05-00 = 1 or 6
(motor is running). Make sure the motor executes auto-tuning under break-away load
condition. Check if there are motor parameters after auto-tuning.
Parameter
Pr.05-06
Pr.05-07
Pr.05-08
Pr.05-09
Motor 1 rated / base frequency (Hz)
Motor 1 rated / base voltage (V
Full-load current for induction motor 1 (A)
Rated power for induction motor 1 (kW)
Rated speed for induction motor 1 (rpm)
Number of poles for induction motor 1 (poles)
Stator resistance (Rs) for induction motor 1 (Ω)
Rotor resistance (Rr) for induction motor 1 (Ω)
Magnetizing inductance (Lm) for induction motor 1 (mH)
Stator inductance (Lx) for induction motor 1 (mH)
466