Delta MS300 Series User Manual page 234

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

Pr.
Explanation
Signal Loss Selection for
03-19
Analog Input 4–20 mA
AFM Multi-Function
03-20
Output
03-21
AFM Analog Output Gain
AFM Analog Output in
03-22
REV Direction
03-27
AFM Output Bias
AVI Terminal Input
03-28
Selection
ACI Terminal Input
03-29
Selection
PLC Analog Output
03-30
Terminal Status
Chapter 11 Summary of Parameter SettingsMS300
0: Disable
1: Continue operation at the last frequency
2: Decelerate to 0 Hz
3: Stop immediately and display "ACE"
0: Output frequency (Hz)
1: Frequency command (Hz)
2: Motor speed (Hz)
3: Output current (rms)
4: Output voltage
5: DC bus voltage
6: Power factor
7: Power
8: Output torque
9: AVI
10: ACI
12: Iq current command
13: Iq feedback value
14: Id current command
15: Id feedback value
16: Vq-axis voltage command
17: Vd-axis voltage command
18: Torque command
19: PG2 frequency command
20: CANopen analog output
21: RS-485 analog output
22: Communication card analog output
23: Constant voltage output
0.0–500.0%
0: Absolute value in output voltage
1: Reverse output 0 V; forward output 0–10 V
2: Reverse output 5–0 V; forward output 5–10 V
-100.00–100.00%
0: 0–10 V (Pr.03-63–Pr.03-68 is valid)
3: -10–10 V (Pr.03-69–Pr.03-74 are valid)
0: 4–20 mA
1: 0–10 V
2: 0–20 mA
Monitor the status of the PLC analog output terminals
bit 0: AFM
225
Settings
Default
0
0
100.0
0
0.00
0
0
Read only

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents