Chapter 13 Warning CodesMS300
ID No.
Display on LCD Keypad
18
Action Condition
Action Time
Warning Setting Parameter
Reset Method
Reset Condition
Record
Cause
Improper parameter setting for the
slip error
Improper setting for ASR
parameter and acceleration/
deceleration
Accel. / Decel. time is too short
Motor locked
Mechanical brake is not released
Incorrect parameter setting of
torque limit
(Pr.06-12, Pr.11-17–20)
Malfunction caused by
interference
Warning Name
Deviation Warning
(dAvE)
Action and Reset
Pr.10-13
Pr.10-14
Pr.10-15 Encoder Stall and Slip Error Action = 0
0: Warn and continue operation
"Warning" automatically clears when the drive stops
After the drive stops
N/A
Reset proper value for Pr.10-13 and Pr.10-14.
Reset ASR parameters.
Set proper accel. / decel. time.
Reset proper accel. / decel. time.
Remove the causes of motor locked.
Check the action timing of the system.
Adjust to proper setting value.
Verify the wiring of the control circuit, and the wiring/grounding of the main circuit
to prevent interference.
486
Description
Over speed deviation warning
Corrective Actions