 Summary of Function Settings
(Take the normally open contact (N.O.) for example, ON: contact is closed, OFF: contact is
open)
Settings
Functions
0
No Function
1
Indication during RUN
Operation speed
2
reached
Desired frequency
3
reached 1 (Pr.02-22)
Desired frequency
4
reached 2 (Pr.02-24)
Zero speed
5
(Frequency command)
Zero speed including
6
STOP
(Frequency command)
7
Over-torque 1
8
Over-torque 2
9
Drive is ready
Low voltage warning
10
(Lv)
11
Malfunction indication
13
Overheat warning
Software brake signal
14
indication
PID feedback error
15
(Pr.08-13, 08-14)
16
Slip error (oSL)
Count value reached,
17
does not return to 0
(Pr.02-20)
Count value reached,
18
returns to 0 (Pr.02-19)
Chapter 12 Descriptions of Parameter SettingsMS300
Output terminal with no function
Activates when the drive is not in STOP.
Activates when output frequency of drive reaches to the setting
frequency.
Activates when the desired frequency (Pr.02-22) is reached.
Activates when the desired frequency (Pr.02-24) is reached.
Activates when Frequency command = 0. (the drive must be in
RUN status)
Activates when Frequency command = 0 or stopped.
Activates when the drive detects over-torque. Pr.06-07 sets the
over-torque detection level (motor 1), and Pr.06-08 sets the over-
torque detection time (motor 1). Refer to Pr.06-06–06-08.
Activates when the drive detects over-torque. Pr.06-10 sets the
over-torque detection level (motor 2), and Pr.06-11 sets the over-
torque detection time (motor 2). Refer to Pr.06-09–06-11.
Activates when the drive is ON with no error detected.
Activates when the DC bus voltage is too low.
(refer to Pr.06-00 Low Voltage Level)
Activates when fault occurs (except Lv stop).
Activates when IGBT or heat sink overheats to prevent the drive
from shutting down due to overheating. (refer to Pr.06-15)
Activates when the soft brake function is ON. (refer to Pr.07-00).
Activates when the PID feedback signal error is detected.
Activates when the slip error is detected.
When the drive executes external counter, this contact activates
if the count value is equal to the setting value for Pr.02-20.
This contact deactivates when the setting value for Pr.02-20 >
Pr.02-19.
When the drive executes the external counter, this contact
activates if the count value is equal to the setting value for Pr.02-
19.