Chapter 13 Warning CodesMS300
ID No.
Display on LCD Keypad
41
Action Condition
Action Time
Warning Setting Parameter
Reset Method
Reset Condition
Record
Cause
Incorrect setting of CANopen
station address
Warning Name
CANopen station
address error (CAdn)
Action and Reset
CANopen station address error
Immediately act when the fault is detected
N/A
Manual Reset
Pr.00-02 = 7
When Pr.00-21 ≠ 3, CAdn is a "Warning", and the warning is not recorded.
1. Disable CANopen (Pr.09-36 = 0)
2. Reset CANopen (Pr.00-02 = 7)
3. Reset CANopen station address (Pr.09-36)
502
Description
CANopen station address error (only supports 1–127)
Corrective Actions