Delta MS300 Series User Manual page 620

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

ID
Display on LCD Keypad
102
Action Condition
Action Time
Fault Treatment Parameter
Reset Method
Reset Condition
Record
Cause
The heartbeat time is too short
Malfunction caused by
interference
Communication cable is broken or
bad connected
Fault Name
CANopen heartbeat
error
(CHbE)
Action and Reset
When CANopen Heartbeat detects that one of the slaves does not respond, the
ChbE fault occurs.
The upper unit sets the confirming time of producer and consumer during
configuration.
The confirming time that the upper unit sets for producer and consumer during
configuration.
N/A
Manual reset
The upper unit sends a reset package to clear this fault
Yes
Increase heartbeat time (Index 100C)
1. Verify the wiring and grounding of the communication circuit. It is
recommended to separate the communication circuit from the main circuit,
or wire in 90 degree for effective anti-interference performance.
2. Make sure the communication circuit is wired in series.
3. Use CANopen cable or add terminating resistance.
Check or replace the communication cable.
611
Fault Descriptions
CANopen heartbeat error
Corrective Actions
Chapter 14 Fault CodesMS300

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents