Parallel connection
08-08
Feedback Signal Detection Time
Settings
 Valid only when the feedback signal is ACI (4–20 mA).
 This parameter sets the detection time for abnormal PID signal feedback. You can also use it
when the system feedback signal response is extremely slow. (Setting the detection time to 0.0
disables the detection function.)
08-09
Feedback Signal Fault Treatment
Settings
 Valid only when the feedback signal is ACI (4–20 mA).
 Sets the treatments when the PID feedback signal is abnormal.
08-10
Sleep Level
Settings
08-11
Wake-up Level
Settings
 Determines the sleep frequency, and if the sleep time and the wake-up frequency are enabled or
disabled.
 Pr.08-10 = 0: Disabled; Pr.08-10 ≠ 0: Enabled
0.0–3600.0 sec.
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
3: Warn and operate at last frequency
0.00–599.00 Hz / 0.00–200.00%
0.00–599.00 Hz / 0.00–200.00%
Chapter 12 Descriptions of Parameter SettingsMS300
403
Default: 0.0
Default: 0
Default: 0.00
Default: 0.00