Chapter 12 Descriptions of Parameter SettingsMS300
03-28
AVI Terminal Input Selection
Settings
03-29
ACI Terminal Input Selection
Settings
 When you change the input mode, verify that the external terminal switch (ACI) position is
correct.
 When you change the setting, proportion to the corresponding AVI and ACI will change to
default.
03-30
PLC Analog Output Terminal Status
Settings
 Example:
When Pr.03-30 displays 0001 (hex) (that is, the value is 1 (decimal) and 1 (binary)), it means
that AFM is used by PLC.
03-31
AFM Output Selection
Settings
0: 0–10 V (Pr.03-63–Pr.03-68 is valid)
3: -10–10 V (Pr.03-69–Pr.03-74 are valid)
0: 4–20 mA
1: 0–10 V
2: 0–20 mA
Monitor the status of the PLC analog output terminals
bit 0: AFM
0: 0–10 V output
1: 0–20 mA output
2: 4–20 mA output
338
Default: 0
Default: 0
Default: Read only
Default: 0