 Related parameters: Pr.01-00 Motor 1 Maximum Operation Frequency, Pr.01-11 Output
Frequency Lower Limit.
 When the drive starts, it operates according to the V/F curve and accelerates from the minimum
output frequency (Pr.01-07) to the setting frequency. It is not limited by the lower output
frequency settings.
 Use the frequency upper and lower limit settings to prevent operator misuse, overheating
caused by the motor's operating at a too low frequency, or mechanical wear due to a too high
speed.
 If the frequency upper limit setting is 50 Hz and the frequency setting is 60 Hz, the maximum
output frequency is 50 Hz.
 If the frequency lower limit setting is 10 Hz and the minimum output frequency setting (Pr.01-07)
is 1.5 Hz, then the drive operates at 10 Hz when the Frequency command is higher than Pr.01-
07 but lower than 10 Hz. If the Frequency command is lower than Pr.01-07, the drive is in ready
status without output.
01-12
Acceleration Time 1
01-13
Deceleration Time 1
01-14
Acceleration Time 2
01-15
Deceleration Time 2
01-16
Acceleration Time 3
01-17
Deceleration Time 3
01-18
Acceleration Time 4
01-19
Deceleration Time 4
01-20
JOG Acceleration Time
Chapter 12 Descriptions of Parameter SettingsMS300
287