01-22
JOG Frequency
Settings
 You can use both the external terminal JOG and F1 key on the optional keypad KPC-CC01
(optional) to set the JOG function. When the JOG command is ON, the AC motor drive
accelerates from 0 Hz to the JOG frequency (Pr.01-22). When the JOG command is OFF, the
AC motor drive decelerates from the JOG frequency to stop. The JOG acceleration and
deceleration time (Pr.01-20, Pr.01-21) are the time to accelerate from 0.00 Hz to the JOG
frequency (Pr.01-22). You cannot execute the JOG command when the AC motor drive is
running. When the JOG command is executing, other operation commands are invalid.
01-23
Switch Frequency between First and Fourth Accel. /Decel.
Settings
 This function does not require the external terminal switching function; it switches the
acceleration and deceleration time automatically according to the Pr.01-23 setting. If you set the
external terminal, the external terminal has priority over Pr.01.23.
 Use this parameter to set the switch frequency between acceleration and deceleration slope.
The First / Fourth Accel. / Decel. slope is calculated by the Max. Operation Frequency (Pr.01-00)
/ acceleration / deceleration time.
Example: When the Max. Operation Frequency (Pr.01-00) = 80 Hz, and Switch Frequency
between First and Fourth Accel. / Decel. (Pr.01-23) = 40 Hz:
a. If Acceleration Time 1 (Pr.01-02) = 10 sec., Acceleration Time 4 (Pr.01-18) = 6 sec., then the
acceleration time is 3 sec. for 0–40 Hz and 5 sec. for 40–80 Hz.
b. If Deceleration Time 1 (Pr.01-13) = 8 sec., Deceleration Time 4 (Pr.01-19) = 2 sec., then the
deceleration time is 4 sec. for 80–40 Hz and 1 sec. for 40–0 Hz.
01-24
S-curve for Acceleration Begin Time 1
01-25
S-curve for Acceleration Arrival Time 2
01-26
S-curve for Deceleration Begin Time 1
01-27
S-curve for Deceleration Arrival Time 2
Settings
0.00–599.00 Hz
0.00–599.00 Hz
Pr.01-45 = 0: 0.00–25.00 sec.
Pr.01-45 = 1: 0.0–250.0 sec.
Chapter 12 Descriptions of Parameter SettingsMS300
289
Default: 6.00
Default: 0.00
Default: 0.20