Delta MS300 Series User Manual page 250

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

Pr.
Explanation
Dwell Frequency at
07-16
Acceleration
07-17
Dwell Time at Deceleration
Dwell Frequency at
07-18
Deceleration
07-19
Fan Cooling Control
Emergency Stop (EF) &
07-20
Force to Stop Selection
Automatic Energy-Saving
07-21
Setting
Automatic Voltage
07-23
Regulation (AVR) Function
Torque Command Filter
07-24
Time
Slip Compensation Filter
07-25
Time
07-26
Torque Compensation Gain
07-27
Slip Compensation Gain
07-29
Slip Deviation Level
Over-Slip Deviation
07-30
Detection Time
Over-Slip Deviation
07-31
Treatment
Chapter 11 Summary of Parameter SettingsMS300
Settings
0.00–599.00 Hz
0.00–600.00 sec.
0.00–599.00 Hz
0: Fan is always ON
1: Fan is OFF after the AC motor drive stops for one
minute.
2: Fan is ON when the AC motor drive runs, fan is OFF
when the AC motor drive stops.
3: Fan turns ON when temperature (IGBT) reaches
o
around 60
C.
0: Coast to stop
1: Stop by the first deceleration time
2: Stop by the second deceleration time
3: Stop by the third deceleration time
4: Stop by the fourth deceleration time
5: System deceleration
6: Automatic deceleration
0: Disable
1: Power factor energy-saving improvement
0: Enable AVR
1: Disable AVR
2: Disable AVR during deceleration
0.001–10.000 sec.
0.001–10.000 sec.
IM: 0–10 (when Pr.05-33 = 0)
PM: 0–5000 (when Pr.05-33 = 1 or 2)
0.00–10.00
0.0–100.0%
0: No detection
0.0–10.0 sec.
0: Warn and continue operation
1: Fault and ramp to stop
2: Fault and coast to stop
241
Default
0.00
0.00
0.00
3
0
0
0
0.050
0.100
1
0.00
(Default value
is 1.00 in SVC
mode)
0
1.0
0