Entering the correct password in Pr.00-07 only temporarily deactivates the password. To
permanently deactivate password protection, set Pr.00-08 to 0 manually. Otherwise, password
protection is always reactivated after you reboot the motor drive.
The keypad copy function works only when the password protection is deactivated (temporarily
or permanently), and the password set in Pr.00-08 cannot be copied to the keypad. So when
copying parameters from the keypad to the motor drive, set the password manually again in the
motor drive to activate password protection.
00-10
Control Mode
Settings
Determines the control mode of the AC motor drive.
When Pr.00-10 = 2: Torque mode, control mode is IM TQC Sensorless.
00-11
Speed Control Mode
Settings
Determines the control mode of the AC motor drive:
0: IM V/F control: you can set the proportion of V/F as required and control multiple motors
0: Speed Control mode
2: Torque mode
0: IMVF (IM V/F control)
1: IMVFPG (IM V/F control + MI7 one-phase pulse input)
2: IM/PM SVC (IM / PM Space Vector Control)
5: IMFOC Sensorless (IM Field-Oriented sensorless vector Control)
Chapter 12 Descriptions of Parameter SettingsMS300
265
Default: 0
Default: 0