Delta MS300 Series User Manual page 168

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

Electrical Specification
Power Supply Voltage
Insulation Voltage
Communication Cable
Power Consumption
Power Consumption
Weight
Environment
Noise Immunity
Operation / Storage
Shock / Vibration
Resistance
DeviceNet Connector
PIN
Signal
1
V+
2
H
3
S
4
L
5
V-
8-3-4 LED Indicator & Troubleshooting
There are two LED indicators on the CMM-DN02: NS LED and MS LED. NS LED and MS LED are
dual-color LEDs, displaying the connection status and error messages of the communication module.
NS LED
LED Status
No power supply or the CMM-DN02
OFF
does not pass the MAC ID test.
Green light
The CMM-DN02 is on-line but does
flashes
not connect to the master.
The CMM-DN02 is on-line and
Green light ON
normally connects to the master.
Red light
The CMM-DN02 is on-line, but I/O
flashes
connection is timed-out.
15 V
(supplied by the AC motor drive)
DC
500 V
DC
0.85 W
1 W
23 g
ESD (IEC 61800-5-1, IEC 6100-4-2)
EFT (IEC 61800-5-1, IEC 6100-4-4)
Surge Test (IEC 61800-5-1, IEC 6100-4-5)
Conducted Susceptibility Test (IEC 61800-5-1, IEC 6100-4-6)
Operation: -10–50ºC (temperature), 90% (humidity)
Storage: -25–70ºC (temperature), 95% (humidity)
International standards:
IEC 61800-5-1, IEC 60068-2-6 / IEC 61800-5-1, IEC 60068-2-27
Color
Red
White
-
Blue
Black
Table 8-16
Indication
159
Chapter 8 Option CardsMS300
Definition
24 V
DC
Signal+
Ground
Signal-
0 V
Corrective Action
1. Check the power to the CMM-DN02 and see if
the connection is normal.
2. Make sure there is at least one node on the
bus.
3. Check if the baud rate of the CMM-DN02 is the
same as that of the other nodes.
1. Configure the CMM-DN02 to the scan list of the
master.
2. Re-download the configured data to the
master.
No action is required.
1. Check if the network connection is normal.
2. Check if the master operates normally.
Table 8-14
Table 8-15
Figure 8-29