8-5 CMM-EIP03
-- (Dual-port) EtherNet/IP, Modbus TCP
8-5-1 Product Profile
Figure 8-34
8-5-2 Features
Supports Modbus TCP and EtherNet/IP protocol
1.
32 / 32 words read / write parameters correspondence
2.
User-defined corresponding parameters
3.
MDI / MDI-X auto-detect
4.
E-mail alarm
5.
IP Filter simple firewall function
6.
8-5-3 Specifications
Network Interface
Interface
Number of Ports
Transmission Method
Transmission Cable
Transmission Speed
Network Protocol
Electrical Specification
Power Supply Voltage
Insulation Voltage
Power Consumption
Weight
Figure 8-35
Wire gauge: 0.25–0.5 mm
Stripping length: 7–8 mm
Torque: 4–6 kg-cm / (3.5–5.2 Ib-in.) / (0.39–0.59 Nm)
RJ45 with Auto MDI / MDIX
1 Port
IEEE 802.3, IEEE 802.3u
Category 5e shielding 100 M
10 / 100 Mbps Auto-Detect
ICMP, IP, TCP, UDP, DHCP, HTTP, SMTP, Modbus TCP, EtherNet / IP, Delta
Configuration
15 V
DC
500 V
DC
1.3 W
30 g
2
/ (24–20 AWG)
165
Chapter 8 Option CardsMS300
1. Screw fixing hole
2. Positioning hole
3. AC motor drive
connection port
4. Communication Port:
P1 (PORT1), P2
(PORT2)
5. Indicator lights: NS, MS
6. Indicator light: POWER
7. Indicator light of LINK: P1
(PORT 1), P2 (PORT 2)
8. Ground terminal block
Table 8-27
Table 8-28