Chapter 12 Description of Parameter SettingsMS300
PM SVC adjustment procedure
(The number marked on the procedure corresponds to the number of following adjustment
explanations)
(1) PM SVC motor parameters adjustment flowchart
PM SVC Adjustment
Procedure
1. AUE auto-tuning error
2. Measured resistance,
inductance or back
EMF error
1. Parameter Reset
Pr.00-02=9 or 10
2. Pr.05-33 Choose motor
=1(SPM) or 2(IPM)
電機參數設定
3. Motor Parameter Setting
Pr01- 01 額定頻率
Pr.01-01 Rated Frequency
Pr01- 02 額定電壓
Pr.01-02 Rated Voltage
Pr.05-34 Full-load Current
Pr.05-35 Rated Power
Pr.05-36 Rated Rotor Speed
Pr.05-37 Motor Poles
4. Motor Parameter Auto-Tuning
Pr.05-00=5
(PM parameters dynamic measuring)
Or Pr.05-00=13
(PM parameters static measuring)
Press 'RUN
Motor
auto-tuning
successful?
NO
YES
5. Set Control Mode
Pr.00-10=0 Speed mode
Pr.00-11=2 PMSVC control
6. Re-power after Power Off
7. Start Initial Angle Detection
Pr.10-53 Angle detection
0: Disable
1: Force attracting the rotor to
zero degree
2: High frequency injection (IPM)
3: Pulse injection (SPM)
8. No-load
Running
458
Check Motor Parameters
Pr.05-39 Rs stator resistance
Pr.05-40 Permanent magnet
motor Ld
Pr.05-41 Permanent magnet
motor Lq
Pr.05-43 Ke parameter
PMSVC mode set "3".
For IPM motor, set"2".
For SPM motor, set "3"
When both "2, 3" do not
perform well, then set
1 .