Delta MS300 Series User Manual page 166

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

Environment
Noise Immunity
Operation / Storage
Shock / Vibration
Resistance
8-2-4 Installation
PROFIBUS DP Connector
PIN
Signal
1
2
3
Rxd / Txd-P
4
5
DGND
6
VP
7
8
Rxd / Txd-N
9
8-2-5 LED Indicator & Troubleshooting
There are two LED indicators on
the status of the working power. NET LED displays the connection status of the communication.
POWER LED
LED Status
Green light ON Power supply in normal status.
OFF
No power
NET LED
LED Status
Green light ON Normal status
The CMM-PD02 is not connected to
Red light ON
PROFIBUS DP bus.
Red light
Invalid PROFIBUS communication
flashes
address
The CMM-PD02 fails to
Orange light
communicate with the AC motor
flashes
drive.
ESD (IEC 61800-5-1, IEC 6100-4-2)
EFT (IEC 61800-5-1, IEC 6100-4-4)
Surge Test (IEC 61800-5-1, IEC 6100-4-5)
Conducted Susceptibility Test (IEC 61800-5-1, IEC 6100-4-6)
Operation: -10–50ºC (temperature), 90% (humidity)
Storage: -25–70ºC (temperature), 95% (humidity)
International standards:
IEC 61131-2, IEC 68-2-6 (TEST Fc) / IEC 61131-2 & IEC 68-2-27(TEST Ea)
-
-
Sending / receiving data P(B)
-
Data reference ground
Power voltage – positive
-
Sending / receiving data N(A)
-
Table 8-9
CMM-PD02: POWER LED and NET LED. POWER LED displays
the
Indication
Indication
Definition
Not defined
Not defined
Not defined
Not defined
Not defined
No action is required.
Check if the connection between the CMM-PD02
and the AC motor drive is normal.
No action is required.
Connect the CMM-PD02 to the PROFIBUS DP bus.
Set the PROFIBUS address of the CMM-PD02
between 1–125 (decimal).
Switch off the power and check whether the CMM-
PD02 is correctly installed and normally connected
to the AC motor drive.
157
Chapter 8 Option CardsMS300
Figure 8-26
Corrective Action
Table 8-10
Corrective Action
Table 8-8
Table 8-11

Hide quick links: