Delta MS300 Series User Manual page 688

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

16-4-4 Common basic program design examples
Start, stop, and protection circuits
Some applications may require a brief close or brief break using a button to start and stop equipment.
A protective circuit must therefore be designed to maintain continued operation in these situations.
This protective circuit may employ one of the following methods.
Example 1: Priority stop protective circuit
When the start N.O. contact X1 = ON, and the stop N.C. contact X2 = OFF, Y1 = ON. If
X2 switches to ON, coil Y1 is no longer electrified, and this is therefore referred to as
priority stop.
Example 2: Priority start protective circuit
When the start N.O. contact X1 = ON, and the stop N.C. contact X2 = OFF, Y1=ON, and
coil Y1 is electrified and protected. If X2 switches to ON, coil Y1 still protects the contact
and continues to be electrified, and this is therefore referred to as priority start.
Example 3: Setting (SET) and reset (RST) command protective circuit
The following diagram shows a protective circuit composed of RST and SET commands.
A priority stop occurs when you place the RST command after the SET command.
Because the PLC executes programs from the top down, at the end of the program,
the state of Y1 indicates whether coil Y1 is electrified. When X1 and X2 both
actuate, Y1 loses power, and this is therefore referred to as priority stop.
A priority start occurs when you place the SET command after the RST command.
When X1 and X2 both actuate, Y1 electrifies, and this is therefore referred to as
priority start.
X2
Y1
STOP
X1
START
Figure 16-36
Figure 16-37
Top priority of stop
X1
X2
Figure 16-38
679
Chapter 16 PLC Function ApplicationsMS300
Y1
Y1
SET
Y1
RST

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents