03-63
AVI Voltage Lowest Point
Settings
03-64
AVI Proportional Lowest Point
Settings
03-65
AVI Voltage Mid-point
Settings
03-66
AVI Proportional Mid-point
Settings
03-67
AVI Voltage Highest Point
Settings
03-68
AVI Proportional Highest Point
Settings
 When you set the positive voltage AVI to the Frequency command, 100% corresponds to Fmax
(Pr.01-00 Maximum Operation Frequency) and the motor runs in the forward direction.
 The requirement for these three parameters (Pr.03-63, Pr.03-65 and Pr.03-67) is Pr.03-63 <
Pr.03-65 < Pr.03-67. The values for three proportional points (Pr.03-64, Pr.03-66 and Pr.03-68)
have no limits. There is a linear calculation between two points.
 The output percentage becomes 0 % when the positive voltage AVI input value is lower than the
lowest point setting.
Example: If Pr.03-63 = 1 V; Pr.03-64 = 10%, then the output becomes 0% when the AVI input is
≤ 1 V. If the AVI input swings between 1 V and 1.1 V, the drive's output frequency oscillates
between 0% and 10%.
03-69
Negative AVI Voltage Lowest Point
Settings
03-70
Negative AVI Proportional Lowest Point
Settings
03-71
Negative AVI Voltage Mid-point
Settings
0.00–10.00 V
-100.00–100.00%
0.00–10.00 V
-100.00–100.00%
0.00–10.00 V
-100.00–100.00%
-10.00–0.00 V
(valid when Pr.03-28 sets as -10–10 V)
-100.00–100.00%
(valid when Pr.03-28 sets as -10–10 V)
-10.00–0.00 V
(valid when Pr.03-28 sets as -10–10 V)
Chapter 12 Descriptions of Parameter SettingsMS300
341
Default: 0.00
Default: 0.00
Default: 5.00
Default: 50.00
Default: 10.00
Default: 100.00
Default: 0.00
Default: 0.00
Default: -5.00

Hide quick links:

Advertisement

Table of Contents