Chapter 14 Fault CodesMS300
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
IGBT temperature
18
detection failure
IGBT hardware failure in temperature detection
(tH1o)
Action and Reset
Action Condition
NTC broken or wiring failure
When the IGBT temperature is higher than the protection level, and detection
Action Time
time exceeds 100 ms, the tH1o protection activates.
Fault Treatment Parameter
N/A
Reset Method
Manual reset
Reset Condition
Immediately reset
Record
Yes
Cause
Corrective Actions
Wait for 10 minutes, and then cycle the power. Check if tH1o protection still
Hardware failure
exists. If yes, return to the factory for repair.
565