Chapter 11 Summary of Parameter SettingsMS300
Pr.
Explanation
External Terminal UP /
02-09
DOWN Key Mode
Acceleration / Deceleration
02-10
Speed of External Terminal
UP/DOWN Keys
Multi-Function Input
02-11
Response Time
Multi-Function Input Mode
02-12
Selection
Multi-Function Output 1
02-13
(RY1)
Multi-Function Output 2
02-16
(MO1)
Multi-Function Output 3
02-17
(MO2)
84: Multi-motor (IM) selection bit 1
0: According to acceleration / deceleration time
1: With constant speed (Pr.02-10)
2: Pulse signal (Pr.02-10)
3: Curve
4: Steps (Pr.02-10)
0.001–1.000 Hz/ms
0.000–30.000 sec.
0000h–FFFFh (0: N.O.; 1: N.C.)
0: No function
1: Indication during RUN
2: Operation speed reached
3: Desired frequency reached 1 (Pr.02-22)
4: Desired frequency reached 2 (Pr.02-24)
5: Zero speed (Frequency command)
6: Zero speed including STOP (Frequency command)
7: Over-torque 1 (Pr.06-06–06-08)
8: Over-torque 2 (Pr.06-09–06-11)
9: Drive is ready
10: Low voltage warning (Lv) (Pr.06-00)
11: Malfunction indication
13: Overheat warning (Pr.06-15)
14: Software brake signal indicator (Pr.07-00)
15: PID feedback error (Pr.08-13, Pr.08-14)
16: Slip error (oSL)
17: Count value reached, does not return to 0 (Pr.02-20)
18: Count value reached, return to 0 (Pr.02-19)
19: External interrupt B.B. input (Base Block)
20: Warning output
21: Over-voltage
22: Over-current stall prevention
23: Over-voltage stall prevention
24: Operation mode
25: Forward command
26: Reverse command
29: Output when frequency ≥ Pr.02-34
220
Settings
Default
0
0.001
0.005
0000
11
0
0