Chapter 5 Main Circuit TerminalsMS300
Frame A
If you install at Ta 50°C above environment, use copper wires that have a voltage rating of 600 V
and are temperature resistant to 90°C or above.
If you install at Ta 50°C environment, use copper wires that have a voltage rating of 600 V and are
temperature resistant to 75°C or 90°C.
For VFD2A5MS11ANSAA and VFD2A5MS11ENSAA models: If you install at Ta 40°C above
environment, use copper wires that have a voltage rating of 600 V and are temperature resistant to
90°C or above.
To be UL installation compliant, you must use copper wires when installing. The wire gauge is
based on a temperature resistance of 75°C, in accordance with UL requirements and
recommendations.
Do not reduce the wire gauge when using high-temperature resistant wires.
Models
VFD1A6MS11ANSAA
VFD1A6MS11ENSAA
VFD2A5MS11ANSAA
VFD2A5MS11ENSAA
VFD1A6MS21ANSAA
VFD1A6MS21ENSAA
VFD2A8MS21ANSAA
VFD2A8MS21ENSAA
VFD1A6MS23ANSAA
VFD1A6MS23ENSAA
VFD2A8MS23ANSAA
VFD2A8MS23ENSAA
VFD4A8MS23ANSAA
VFD4A8MS23ENSAA
VFD1A5MS43ANSAA
VFD1A5MS43ENSAA
VFD2A7MS43ANSAA
VFD2A7MS43ENSAA
VFD1A7MS53ANSAA
Main Circuit Terminals
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3, DC-,
DC+/+1, +2/B1, B2
Max. Wire
Min. Wire
Gauge
Gauge
2.5 mm
(14 AWG)
1.5 mm
(16 AWG)
2.5 mm
(14 AWG)
2
2.5 mm
0.75 mm
(14 AWG)
(18 AWG)
1.5 mm
(16 AWG)
0.75 mm
(18 AWG)
Figure 5-8
Screw Size &
Max. Wire
Torque
Gauge
(±10%)
2
2
2
M3.5
9 kg-cm
2.5 mm
2
(7.8 lb-in.)
(14 AWG)
(0.88 Nm)
2
2
32
Grounding Terminals
Screw Size &
Min. Wire
Torque
Gauge
(±10%)
M3.5
2
2
2.5 mm
9 kg-cm
(14 AWG)
(7.8 lb-in.)
(0.88 Nm)
Table 5-3