Chapter 14 Fault CodesMS300
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
CANopen index setting
107
exceed limit
CANopen memory error
(CFrE)
Action and Reset
When you update the firmware version of the control board, the FRAM internal
Action Condition
data does not change, then CFrE fault occurs.
Action Time
Immediately act
Fault Treatment Parameter
N/A
Reset Method
Manual reset
Reset Condition
Pr.00-02 = 7
Record
Pr.00-21 = 3, the fault is recorded
Cause
Corrective Actions
1. Disable CANopen (Pr.09-36 = 0)
CANopen internal memory error
2. Reset CANopen (Pr.00-02 = 7)
3. Reset CANopen station address (Pr.09-36)
615