Chapter 12 Descriptions of Parameter SettingsMS300
Settings
12
Output stop
Cancel the setting of
auto-acceleration /
13
auto-deceleration
time
Rotating speed
15
command from AVI
Rotating speed
16
command from ACI
Force to stop
18
(Pr.07-20)
Frequency up
19
command
Frequency down
20
command
PID function
21
disabled
22
Clear the counter
Input the counter
23
value (MI6)
Functions
ON: the output of the drive stops immediately and the motor is
in free run status. The drive is in output waiting status until the
switch is turned to OFF, and then the drive restarts and runs to
the current setting frequency.
Set Pr.01-44 to one of the 01–04 setting modes before using
this function. When this function is enabled, OFF is for auto
mode and ON is for linear acceleration / deceleration.
ON: force the source of the drive's frequency to be AVI. If the
rotating speed commands are set to AVI and ACI at the same
time, the priority is AVI > ACI.
ON: force the source of the drive's frequency to be ACI. If the
rotating speed commands are set to AVI and ACI at the same
time, the priority is AVI > ACI.
ON: the drive ramps to a stop according to the Pr.07-20 setting.
ON: the frequency of the drive increases or decreases by one
unit. If this function remains ON continuously, the frequency
increases or decreases according to Pr.02-09 / Pr.02-10.
The Frequency command returns to zero when the drive stops
and the displayed frequency is 0.00 Hz. If you select Pr.11-00,
bit 7 = 1, the frequency is not saved.
ON: the PID function is disabled.
ON: the current counter value is cleared and displays 0. The
drive counts up when this function is disabled.
ON: the counter value increases by one. Use the function with
Pr.02-19.
Descriptions
300