Delta MS300 Series User Manual page 302

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

 3 (auto-acceleration and auto-deceleration–decelerating by the actual load): the drive auto-
detects the load torque and automatically accelerates from the fastest acceleration time and
smoothest start-up current to the setting frequency. During deceleration, the drive automatically
determines the loaded regenerative energy to steadily and smoothly stop the motor in the fastest
deceleration time.
 4 (stall prevention by auto-acceleration and deceleration–reference to the acceleration and
deceleration time settings): if the acceleration and deceleration time are within a reasonable
range, the actual acceleration and deceleration time refer to the Pr.01-12–01-19 settings. If the
acceleration and deceleration time are too short, the actual acceleration and deceleration time
are greater than the acceleration and deceleration time settings.
01-45
Time Unit for Acceleration and Deceleration and S-Curve
Settings
01-46
CANopen Quick Stop Time
Settings
 Sets the time required to decelerate from the maximum operation frequency (Pr.01-00) to 0.00
Hz through the CANopen control.
01-49
Regenerative Energy Restriction Control Method
Settings
 0: decelerate or stop in accordance with the original deceleration setting.
0: Unit 0.01 sec.
1: Unit 0.1 sec.
Pr.01-45 = 0: 0.00–600.00 sec.
Pr.01-45 = 1: 0.0–6000.0 sec.
0: Normal deceleration
1: Over voltage energy restriction
2: Traction energy control (TEC)
Chapter 12 Descriptions of Parameter SettingsMS300
293
Default: 0
Default: 1.00
Default: 0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents