Chapter 6 Control TerminalsMS300
Terminals
Terminal Function
Digital frequency signal output
DFM
Digital control /
DCM
Frequency signal common
(Sink)
Multi-function Output 1
MO1
(photo coupler)
Multi-function Output 2
MO2
(photo coupler)
Multi-function Output Common
MCM
(photo coupler)
Multi-function relay output 1
RA
(N.O.) a
Multi-function relay output 1
RB
(N.C.) b
RC
Multi-function relay common
+10 V
Potentiometer power supply
DFM uses pulse voltage as an output monitoring signal;
Duty-cycle: 50%
Min. load impedance R
Max. current endurance: 30 mA
Max. voltage: 30 V
± 1 %
DC
(when 30 V
Max. output frequency: 33 kHz
Current-limiting resistor R: ≥ 1 KΩ
Output load impedance R
Capacitive load ≤ 100 pF
Resistive load ≥ 1 kΩ, resistance determines the output
voltage value.
DFM-DCM voltage = external voltage × (R
The AC motor drive outputs various monitoring signals,
such as drive in operation, frequency reached, and overload
indication through a transistor (open collector).
Max. 48 V
50 mA
DC
Resistive Load
3 A (N.O.) / 3 A (N.C.) 250 V
5 A (N.O.) / 3 A (N.C.) 30 V
Inductive Load (COS = 0.4)
1.2 A (N.O.) / 1.2 A (N.C.) 250 V
2.0 A (N.O.) / 1.2 A (N.C.) 30 V
To output different kinds of monitoring signals such as
motor drive in operation, frequency reached, and overload
indication.
Power supply for analog frequency setting: +10.5 ± 0.5 V
/ 20 mA
44
Description
: 1 kΩ / 100 pF
L
/ 30 mA / RL=100 pF)
DC
L
÷ (R
L
Figure 6-9
Figure 6-10
AC
DC
AC
DC
+R) )
L
DC