Chapter 12 Descriptions of Parameter SettingsMS300
 Control by PC (Computer Link)
When using the RS-485 serial communication interface, you must specify each drive's
communication address in Pr.09-00. The computer then implements control using the drives'
individual addresses.
 Modbus ASCII (American Standard Code for Information Interchange): Each byte of data is the
combination of two ASCII characters. For example, one byte of data: 64 Hex, shown as '64' in
ASCII, consists of '6' (36Hex) and '4' (34Hex).
09-09
Communication Response Delay Time
Settings
 If the host controller does not finish the transmitting/receiving process, you can use this
parameter to set the response delay time after the AC motor drive receives communication
command as shown in the following picture.
09-10
Communication Main Frequency
Settings
 When you set Pr.00-20 to 1 (RS-485 communication input), the AC motor drive saves the last
Frequency command into Pr.09-10 when there is abnormal power off or momentary power loss.
When power is restored, the AC motor drive operates with the frequency in Pr.09-10 if there is
no new Frequency command input. When a Frequency command of 485 changes (the
Frequency command source must be set as Modbus), this parameter also changes.
09-11
Block Transfer 1
09-12
Block Transfer 2
4: 7, E, 2 (ASCII)
5: 7, O, 2 (ASCII)
6: 8, N, 1 (ASCII)
7: 8, N, 2 (ASCII)
8: 8, E, 1 (ASCII)
9: 8, O, 1 (ASCII)
10: 8, E, 2 (ASCII)
11: 8, O, 2 (ASCII)
12: 8, N, 1 (RTU)
13: 8, N, 2 (RTU)
14: 8, E, 1 (RTU)
15: 8, O, 1 (RTU)
16: 8, E, 2 (RTU)
17: 8, O, 2 (RTU)
0.0–200.0 ms
0.00–599.00 Hz
416
Default: 2.0
Default: 60.00