Delta MS300 Series User Manual page 378

Standard compact drive
Hide thumbs Also See for MS300 Series:
Table of Contents

Advertisement

06-30
PTC Level
Settings
 Sets AVI / ACI analog input function Pr.03-00–03-01 to 6 [thermistor (PTC) input value)].
 Use this parameter to set the PTC level; 100% PTC level corresponds to the maximum analog
input value.
 When using the AVI terminal, you must set Pr.03-28 to 0 and switch AVI voltage to 0–10 V. At
this time, the AVI input impedance is 20 kΩ.
 When the temperature reaches to the set protection level, the motor acts according to the
settings for Pr.06-29 and displays warning "oH3" (if Pr.06-29 = 1–3). When the temperature is
lower than the set protection level, you can press RESET key to clear the fault.
 The PTC uses the AVI-input and is connected through divider resistance as shown below:
The voltage between +10V to ACM: lies within 10–11V.
1.
The impedance for AVI is around 20K Ω. Recommended value for divider resistance is 1K–
2.
10K Ω.
Please contact your motor dealer for the curve of temperature and resistance value for
3.
PTC.
Protection level (Pr.06-30) = V+10 × (RPTC//20K) ÷ [R1+(RPTC//20K)]
V+10: voltage between +10V-ACM actual value
RPTC: motor PTC overheat protection level;
20K Ω: the AVI input impedance;
R1: divider resistance (recommended value: 1–10k Ω)
Take the standard PTC thermistor as an example: if the protection level is 1330 Ω, the actual
voltage between +10V-ACM is 10.5 V and divider resistance R1 is 4.4k Ω.
0.0–100.0%
Chapter 12 Descriptions of Parameter SettingsMS300
369
Default: 50.0