Chapter 7 Optional AccessoriesMS300
7-2 Magnetic Contactor / Air Circuit Breaker and Non-fuse Circuit Breaker
Magnetic Contactor (MC) and Air Circuit Breaker (ACB)
It is recommended the surrounding temperature for MC should be ≥ 60°C and that for ACB should be ≥
50°C. In the meanwhile, consider temperature derating for components with ON / OFF switch in
accordance with the ambient temperature of the on-site distribution panel.
115V Models
Frame
Model
VFD1A6MS11ANSAA
A
VFD2A5MS11ANSAA
C
VFD4A8MS11ANSAA
230V Models
Frame
Model
VFD1A6MS21ANSAA
VFD2A8MS21ANSAA
A
VFD1A6MS23ANSAA
VFD2A8MS23ANSAA
VFD4A8MS23ANSAA
VFD1A6MS21AFSAA
VFD2A8MS21AFSAA
B
VFD4A8MS21AFSAA
VFD4A8MS21ANSAA
VFD7A5MS23ANSAA
VFD7A5MS21ANSAA
VFD11AMS21ANSAA
VFD7A5MS21AFSAA
C
VFD11AMS21AFSAA
VFD11AMS23ANSAA
VFD17AMS23ANSAA
D
VFD25AMS23ANSAA
VFD33AMS23ANSAA
E
VFD49AMS23ANSAA
F
VFD65AMS23ANSAA
Heavy Duty
Input Current (A)
Output Current (A)
6
9.4
18
Heavy Duty
Input Current (A)
Output Current (A)
5.1
7.3
1.9
3.4
5.8
5.1
7.3
10.8
10.8
9
16.5
24.2
16.5
24.2
13.2
20.4
30
39.6
58.8
78
52
Heavy Duty
MC/ACB Selection
1.6
2.5
4.8
Heavy Duty
MC/ACB Selection
1.6
2.8
1.6
2.8
4.8
1.6
2.8
4.8
4.8
7.5
7.5
11
7.5
11
11
17
25
33
49
65
(A)
11
18
32
Table 7-6
(A)
9
13
9
9
11
9
13
18
18
18
32
40
32
40
22
32
55
65
105
130
Table 7-7