Chapter 13 Warning CodesMS300
ID No.
Display on LCD Keypad
45
Action Condition
Action Time
Warning Setting Parameter
Reset Method
Reset Condition
Record
Cause
Serious interference on hardware
Incorrect setting for
communication speed
The communication card is not
connected, or the card is loose
Warning Name
CANopen start-up
error warning (Cbtn)
Action and Reset
When the amount of sent error messages reach 255
N/A
Index 6007
Disable CANopen, and cycle the power after power-off
N/A
N/A
Verify if the grounding, terminating resistance and bus line are properly
installed.
Verify the setting for communication speed.
Make sure the communication card is connected to the drive.
506
Description
CANopen start-up error warning
Corrective Actions