ID
Display on LCD Keypad
61
Action Condition
Action Time
Fault Treatment Parameter
Reset Method
Reset Condition
Record
Cause
The electromagnetic valve
operates incorrectly during Y-Δ
switch.
Incorrect parameter setting
Y-
The wiring of
Δ switch function is
incorrect
Fault Name
Y-connection / Δ-
connection
switch error
(ydc)
Action and Reset
1. ydc occurs when the confirmation signals of Y-connection and Δ-connection
are conducted at the same time.
2. If any of confirmation signals is not conducted within Pr.05-25, ydc occurs.
Pr.05-25
N/A
Manual reset
Can be reset only when the confirmation signal of Y-connection is conducted if
it is Y-connection, or when the confirmation signal of Δ-connection is conducted
if it is Δ-connection.
Yes
Check if the electromagnetic valve works normally.
If not, replace it.
Check if related parameters are all set up and set correctly.
Check the wiring.
595
Fault Descriptions
Y-
An error occurs when
Corrective Actions
Chapter 14 Fault CodesMS300
Δ switches