Chapter 16 PLC Function ApplicationsMS300
Command
MPP
Read stack
Operand
Retrieves the result of the previously saved logical operation from the stack, and saves
to the cumulative register. (subtract one from stack pointer)
Ladder diagram:
Command
OUT
Drive coil
X0–X17
Operand
Outputs the result of the logical operation before the OUT command to the designated
element.
Coil contact action:
Ladder diagram:
Y0–Y17
Result:
Coil
FALSE
OFF
TRUE
ON
X1
X0
Function
N/A
Function
M0–M799
T0–159
Out command
Access Point:
Contact A (N.O.) Contact B (N.C.)
Not conducting
Conducting
Conducting
Not conducting
Y1
698
Command code:
Description:
LD
X0 Load Contact A of X0
MPS
Save to the stack
Create a series
AND
X1
connection to
contact A of X1
OUT
Y1 Drive Y1 coil
Read the stack
MRD
(pointer does not
change)
Create a series
AND
X2
connection to
contact A of X2
OUT
M0 Drive M0 coil
MPP
Read stack
OUT
Y2 Drive Y2 coil
END
Program conclusion
C0–C79
Command code:
Description:
Load Contact B of
LD
X0
X0
Establish a parallel
AND
X1
connection to
contact A of X1
Y1 Drive Y1 coil
OUT