Chapter 12 Descriptions of Parameter SettingsMS300
Settings
Functions
External interrupt B.B.
19
input (Base Block)
20
Warning output
21
Over-voltage
Over-current stall
22
prevention
Over-voltage stall
23
prevention
24
Operation mode
25
Forward command
26
Reverse command
Output when frequency
29
≥ Pr.02-34
Output when frequency
30
< Pr.02-34
Y-connection for the
31
motor coil
∆-connection for the
32
motor coil
Zero speed
33
(actual output frequency)
Zero speed including
34
stop
(actual output frequency)
Error output selection 1
35
(Pr.06-23)
Error output selection 2
36
(Pr.06-24)
Error output selection 3
37
(Pr.06-25)
Error output selection 4
38
(Pr.06-26)
Speed reached
40
(including Stop)
42
Crane function
Actual motor speed
43
detection
44
Low current output
Activates when external interrupt (B.B.) stop output occurs in the
drive.
Activates when a warning is detected.
Activates when over-voltage is detected.
Activates when the over-current stall prevention is detected.
Activates when over-voltage stall prevention is detected.
Activates when the source of operation command is not
controlled by the digital keypad (Pr.00-21 ≠ 0).
Activates when the operation direction is forward.
Activates when the operation direction is reverse.
Activates when frequency is ≥ Pr.02-34
(actual output H ≥ Pr.02-34).
Activates when frequency is < Pr.02-34
(actual output H
Pr.02-34).
<
Activates when Pr.05-24 = 1, the frequency output is lower than
Pr.05-23 minus 2 Hz and the time is longer than Pr.05-25.
Activates when Pr.05-24 = 1, the frequency output is higher than
Pr.05-23 plus 2 Hz and the time is longer than Pr.05-25.
Activates when the actual output frequency is 0
(the drive is in RUN mode).
Activates when the actual output frequency is 0 or stopped.
Activates when Pr.06-23 is ON.
Activates when Pr.06-24 is ON.
Activates when Pr.06-25 is ON.
Activates when Pr.06-26 is ON.
Activates when the drive's output frequency reaches the setting
frequency or stopped.
Use this function with Pr.02-34 and Pr.02-58.
Refer to Pr.02-34 and 02-58 for details and application examples.
Activates when the motor actual speed is less than Pr.02-47.
Use this function with Pr.06-71–Pr.06-73.
310
Descriptions