Chapter 12 Descriptions of Parameter SettingsMS300
05-05
No-Load Current for Induction Motor 1 (A)
Settings
 The default is 40% of the motor's rated current.
05-06
Stator Resistance (Rs) for Induction Motor 1
Settings
05-07
Rotor Resistance (Rr) for Induction Motor 1
Settings
05-08
Magnetizing Inductance (Lm) for Induction Motor 1
05-09
Stator Inductance (Lx) for Induction Motor 1
Settings
05-13
Full-Load Current for Induction Motor 2 (A)
Settings
 Set this value according to the rated current of the motor as indicated on the motor nameplate.
The default is 90% of the drive's rated current.
Example: The rated current for a 7.5 HP (5.5 kW) motor is 25 A. The default is 22.5 A.
The setting range is 2.5–30 A (25 × 10% = 2.5 A and 25 × 120% = 30 A).
05-14
Rated Power for Induction Motor 2 (kW)
Settings
 Sets the rated power for motor 2. The default is the drive's power value.
05-15
Rated Speed for Induction Motor 2 (rpm)
Settings
 Sets the rated speed for the motor as indicated on the motor nameplate.
05-16
Number of Poles for Induction Motor 2
Settings
 Sets the number of poles for the motor (must be an even number).
0.00–Pr.05-01 default
0.000–65.535 Ω
0.000–65.535 Ω
0.0–6553.5 mH
10–120% of the drive's rated current
0.00–655.35 kW
0–xxxxx rpm (Depending on the motor's number of poles)
1710 (60 Hz 4 poles); 1410 (50 Hz 4 poles)
2–20
346
Default: Depending on the
model power
Default: Depending on the
model power
Default: 0.000
Default: 0.0
Default: Depending on the
model power
Default: Depending on the
model power
Default: Depending on the
motor's number of poles
Default: 4